1- Resistance thermometer for building automation, machine construction and environmental engineering

Different output signals
- Pt 100 signal
- 4...20 mA, temperature linear, analog
- 4...20 mA, HART protocoll (on request)
Short response time
Models for intrinsic safe circuits available
High operational reliability
- Long term stability
- Maintanance free
Resistance thermometer
Model |
Type |
Possible applications |
 |
Air duct temperature sensor |
Air ducts |
 |
Average temperature sensor |
Air registers Air ducts Air shafts Environmental protection |
 |
Pipeline temperature sensor |
Water pipes Heating pipes Sewage pipes Mechanical engineering |
 |
Pipeline and air duct temperature sensor with exchangeable measuring inset |
Air ducts, water pipes, heating pipes, sewage pipes, mechanical engineering, environmental engineering |
 |
Pipeline and air duct temperature sensor |
Air ducts, water pipes, heating pipes, sewage pipes, mechanical engineering, environmental engineering |
 |
Pipeline and air duct temperature sensor with quick-release connector |
Air ducts, water pipes, heating pipes, sewage pipes, mechanical engineering, environmental engineering |
Dimensions, wiring diagrams
2- Resistance thermometers for the use in pipes, airducts and processing apparatus
Essential components
- Rapid connection technology
- Connection head type B
- Optional head transmitter
- Tough protection tube design
- Adjust. compression fitting respectively sheet-metal flange
Technical features
- High vibration resistance because of tough construction
- Fast response
- Connection head with degree of protection IP 67
- Transmitter EMC to NAMUR recommendation NE 21
- automatically pull relief
Applications
- Chemical industry
- Food and beverage industry
- HVAC
- Machinery industry
Technical data

- Resistance element : 1 x Pt 100
- Standard tolerance : EN 60751, class B
- Circuit type : 3-wire circuit
- Measuring range : -40...200 °C
- Protection tube :
- Ø 8 x 2 mm,
- material 1.4571 (AISI 316-TI)
- Process connection:
- Adjustable compression fitting,
- G½“, 1/2“ NPT thread,
- Material: galvanized steel, steel compression ring
- Sheet-metal flange, chromised, diameter 90 mm
- Nominal length : 50, 100, 150, 250, 400 mm
- Connection head : Type B, degree of protection IP 67
- Cable entry : Rapid connection technology
- Response time
- Water 4 s (T05, v = 0.4 m/s)
- Air 60 s (T05, v = 3 m/s)
Technical data sensor head transmitter
- Input
- Pt 100 (EN 60751),
- 3-wire circuit, fixed ranges
- Output : 4...20 mA, temperature linear
- Power supply : Us = 10.5...30 V DC, polarity safe
- Climatic conditions
- Ambient temperature : -40...85 °C
- Relative humidity : ≤ 100 % (condensation possible)
- Characteristics at rated conditions1)
- Measurement deviation (upper-range value)
- nominal value 0 °C: ≤ 0.15 % or 0.15 K
- nominal value < or > 0 °C: ≤ 0.2 % or 0.2 K
- Deviation of linearity : < 0.10 %
- Electromagnetic compatibility : according to NAMUR NE 21
- CE conform
- Measuring range ot the sensor head transmitter
- -30...+ 60 °C or
- -20...+100 °C or
- -40...+150 °C or
- -40...+200 °C
3- Resistance thermometers with welded protection tube and measuring inset
4- Resistance thermometers for installation in a thermowell, with measuring inset